The panel is designed for use in fire alarm and notification systems installed in premises for fire detection, as well as for notification and transmission of information to external equipment and to the CPAS indication equipment.
FEATURES:
the panel allows connection of up to 32 active call points or up to 10 manual fire detectors to a single fire alarm system using a two-wire circuit;
allows connection of Art-SP2, Art-HP1, SP-2.1 active fire detectors manufactured by Arton to the fire alarm system without installing current-limiting resistors;
is powered from mains supply with a voltage 230 with a tolerance of minus 15% and plus 10%) and afrequency of (50±1) Hz. Two sealed, maintenance-free lead-acid batteries with anominal voltage of 12 V and a nominal current of 7 Ah each are used as a backuppower source for the panel;
provides battery operation for at least 24 hours in standby mode and 30 minutes in "FIRE" mode;
provides signals using the following output keys: freely programmable output("OUT1","OUT2","OUT3"; "OUT4"), relay output of the "Fire" signal("FIRE"), relay output for the "Fault" signal("FAULT");
provides multi-level access to control functions;
provides status indication via a display and LED indicators;
using the built-in keyboard and display, the panel allows you to view and configure (programming) of parameters and operating functions;
automatically detects and displays the following types of faults and conditions(see manual);
operating temperature range from minus 5 to 40 °С.
Specifications
The overall dimensions of the panel are no more than: 290x253x80 mm: not more than 290х253х80 mm;
Weight of the panel without the battery – no more than3,5 kg: no more than 3,5 kg;
Ingress protection: ІР30;
The panel is powered from an AC mains supply with a voltage of 230 V (with a tolerance of minus 15% and plus 10%) and a frequency of (50±1) Hz;
Two sealed, maintenance-free lead-acid batteries with a nominal voltage of 12 V and a nominal current of 7 Ah each are used as a backup power source for the panel;
Maximum power consumption: 35 W;
2.8 Long-term current consumption of the PWR: no more than 1.9 A;
Maximum long-term current consumption of the panel from the battery:1,3 A;
Minimum current consumption of the panel from the battery: 0,2 A;
Maximum number of fire alarm systems connected to the panel: 16;
Supply voltage of the power supply unit without load: (24 ± 0,5) V;
The voltage at the contacts of the circuit breaker at a current in each of the circuit breakers up to 45 mA: not less than 22 V;
The current value in the circuit of the circuit breaker, which is assessed as the state of the circuit breaker: from 3.5 mA to 18 mA;
The value of the current increase in the AL, which is assessed by the panel as the "ATTENTION" state from the automatic detector: from 6 mA to 12 mA, relative to the normal level, but not more than 19 mA;
The value of the current increase in the fire alarm system, which is assessed by the panel as a "FIRE" status from the manual alarm panel: from 6 mA to 50 mA;
The current in the fire alarm system, which is assessed by the panel as a break: less than 3.2 mA;
The current in the fire alarm system, which is assessed by the panel as a short circuit: more than 50 mA;
The maximum load current for each of the outputs «OUT1»…«OUT4»: 400 mA;
The total load current of the outputs must be: no more 1 A;
The duration of automatic reset (shutdown time) of the short circuit in case of manual reset or short circuit verification: (5 ±1) s;
Тhe duration of waiting for the alarm to activate in the fire alarm system in the "ATTENTION" state, upon detection of which the panel switches to the "FIRE" mode: 5 minutes;
The average service life of the panel: at least 10 years;