SPD-3.1Ì


* — with the base B103-01.


The fire smoke optical point detector SPD-3.1M is designed for the detection of ignitions in enclosed premises of various buildings and constructions which are accompanied with the appearing of smoke and for the transmission the “Fire” signal to a control panel. The detector is counted on the continuous operation along with a control panel by a 2-wire fire alarm loop with the nominal voltage of the loop power voltage 12 or 24 V.

Detectors SPD-3.1M can be completed with the base B103-01, which has an additional free contact (the screw joint) “5”. This contact is meant for the ease of assembling terminal (Rterm) and limiting (Rlim) resistors.

The loop matching module MUSH-2 is applied for the connection of detectors to a control panel with the 4-wire connection scheme of detectors.


Technical specifications of the smoke detector SPD-3.1M


Sensitivity, dB/m0,05—0,2
Lag, s≤ 10
Power voltage range, V10—30
Way of output signal forming Non-contact
Consumption current in standby mode, mA≤ 0,095
Consumption current in “Fire” mode, mA6—36
Internal resistance in “Fire” mode, Ω≤ 500
Dimensions, mmØ100×48
Mass, kg0,15
Operating temperature range, °Ñ-30 ... + 55
Average service life, years≥ 10