MUSH-3

Loop matching modules


MUSH-3



The module is designed for the match of 2-wire alarm loop with fire and intrude-fire control panels operating with 4-wire alarm loop, and also to a control panel with A.C. power supply of an alarm loop.

When any of detectors activates in the 2-wire loop circuit, the module forms the “Fire” signal by spasmodic reduction of resistance in the signal line circuit of 4-wire loop of a control panel, which is indicated by the switch a red optical indicator on the module.

The module forms the “Fault” signal by the open-circuit in a signal line of a 2-wire alarm loop when detecting the following events:

  • Open-circuit of a 2-wire alarm loop;
  • Short-circuit of a 2-wire alarm loop;
  • Absence of the power voltage 12 v.

The module provides the indication of:

  • The standby operational mode with a green optical indicator;
  • The “Fault” signal with a yellow optical indicator.

The module provides the restriction of the short-circuit current of a 2-wire loop.

The module allows switching off the power supply of a 2-wire alarm loop for a short term with the help of the “Discharge” button.


Technical specifications of the loop matching module MUSH-3


Nominal power voltage of the Module, V12
Power voltage range, that the Module keeps the operation ability with, V10,2—13,8
Voltage range powering a 2-wire loop in the standby mode, V9,7—13,6
Magnitude of stepping-down voltage on the module in the standby mode, V≤ 0,5
Short-circuit current in a 2-wire loop circuit, mA≤ 20
Current in a 2-wire loop circuit with which the module forms the optical signal “Fault”, mA≤ 3,0
Current in a 2-wire loop circuit with which the module forms the optical signal “standby mode”, mA4,5—7,5
Current in a 2-wire loop circuit with which the module forms the optical signal “Fire”, mA8,5—19,5
Resistance of a 2-wire loop (without taking into account the resistance of an output element), that the Module keeps its operational capability with, Ω≤ 100
Quantity of fire detectors connected to a 2-wire loop≤ 32
Consumption current in the standby mode, mA≤ 20
Consumption current in the “Fire” mode, mA≤ 40
Current consumed by the module on the 2-wire open-circuit, mA≤ 13
Current consumed by the module on the 2-wire short-circuit, mA≤ 31
Commutated voltage of a signal loop, V≤ 30
Current drawing through contacts «1», «2» è «3», «4» in a signal loop circuit, mA≤ 30
Voltages in contacts «1», «2» è «3», «4» with current 20 mA, V≤ 1,6
Resistance between contacts «1», «2» è «3», «4» in the “Fault” mode, kΩ≥ 300
Dimensions, mm 70×70×30
Mass, kg0,05
Ambient temperature, °Ñ+1 ... +40
Relative air humidity at +35 °Ñ, %≤ 95