MUSH-2

Loop matching modules


MUSH-2



The module is designed for the match of a 2-wire alarm loop with fire and intruder-fire control panels operating with a 4-wire alarm loop.

The module forms the “Alarm” signal for a control panel and induces this status by a red optical indicator when detecting the following events:

  • Activation of one or several fire detectors in the 2-wire loop circuit;
  • Open-circuit or short-circuit in the 2-wire loop circuit;
  • Absence of power voltage 12V.

The forming of the “Fire” signal is performed by open-circuit of a signal line in a 4-wire loop.

The module provides:

  • Indication of the standby mode by a green optical indicator;
  • Restriction of the short-circuit current on the specified level.

Modules allow disconnecting the power supply of a 2-wire loop for a short duration with the help of the discharge button.


Technical specifications of the loop matching module MUSH-2


Inlet voltages’ range, V10,2—13,8
Outlet voltages’ range in the standby mode, V9,7—13,3
Magnitude of dropping voltage on the module in the standby mode, V≤ 0,5
Short-circuit current in a 2-wire loop’s circuit, mA30 ± 3
Current in a 2-wire loop circuit interpreted by the module as “Open-circuit”, mA≤ 4,0
Current in a 2-wire loop circuit interpreted by the module as the standby mode, mA5,0—13,5
Current in a 2-wire loop’s circuit interpreted by the module as the “Alarm” mode, mA≥ 16,5
Consumption current from a source 12V in the ”Open-circuit” mode of a 2-wire loop, mA≤ 15
Consumption current from a source 12V in the standby mode, mA≤ 12 + consumption current of a 2-wire loop
Consumption current from a source 12V in the ”Short-circuit” mode of a 2-wire loop, mA ≤ 45
Commutated voltage of a signal loop, V ≤ 60
Commutated current in the circuit of a signal loop, mA ≤ 100
Resistance between contacts “3” and “2” in the standby mode, Ω≤ 50
Dimensions, mm 70×70×30
Mass, kg0,05