The control panel “ARTON-04P” is designed for the arrangement of centralized and autonomous protection of various objects against fire by the 24-hours control of the status up to 4 fire alarm loops.
The control panel “ARTON-04P” conforms to all the norms of DSTU EN54-2:2003 and DBN V 2.5-13-98.
The control panel “ARTON-04P” controls and reflects with optical indicators alarm statuses (alarm loops): the standby mode, the verification of an alarm loop (if AL is with verification), “Fire”, “Short-circuit”, “Open-circuit”, “AL switched-off”.
The device controls and reflects with optical indictors the following kinds of faults and statuses:
- The short-circuit of output switches;
- The open-circuit of output switches’ loads “Light/Sound”, “Fire” and “Fault”;
- The absence of power voltage of output switches and AL;
- The absence of A.C. mains 220 V;
- The critical discharge or the absence of a storage battery;
- The fault of a charger;
- A system error.
The protection against an unsanctioned access inside a case is provided in the device (opening or breaking of the cover). When opening the cover, a tamper button activates and the device passes to the “Alarm” mode.
The device is meant for the connection of 2- and 4-wire alarm loops. The connection both active and passive detectors is possible as well as the combined connection of detectors.
The device provides:
- Automatic charging of a storage battery and the protection against its improper connection;
- Protection of all the output switches against the short-circuit with automatic restoration of the initial status after the elimination of the short-circuit;
- Multilevel access to management functions.
With the help of a built-in keyboard it is possible to programme the following parameters and functions:
- The survey and determination the type of alarm loop zone (with/without verification);
- Fixation of the basic current of AL;
- Setting of consumer rights for the management of AL;
- Change of consumers’ and an engineer’s passwords;
- Setting of an operational mode of a light-sound detector;
- Setting of activation time of a light-sound detector;
- Setting of a mode and programming of operation logics of additional output switches;
- Reset to factory settings.