Question: How should modules “MUSH-DL” be used for the connection of two-wire detectors SPD-2.1, SPD-3, SPD-3.1, SPD-3.1M to a control panel with the 4-wire scheme of connection?
Answer:
It is possible to organize the functioning of modules in 2 modes:
- Nominal load;
- Maximum load;
The open-circuit in any place of alarm loops shall be interpreted as a fault in the nominal load mode.
The summary consumption current of detectors must not exceed the threshold of a module’s open-circuit. The maximum quantity of detectors is determined by the formula:
Ndet = Ibr / Ij (1)
Where Ndet — maximum quantity of detectors in an alarm loop; Ibr — threshold of determination the status “Open-circuit” by “MUSH-DL”; Ij — consumption current of a detector in the standby mode.
For serially manufactured detectors SPD-2.1 and for a module MUSH-DL:
Ibr = 1,6 mA
Ij = 0,22 mA
Ndet = 1,6/0,22 ≈ 7 pcs.
For serially manufactured detectors SPD-3, SPD-3.1, SPD-3.1M and for a module MUSH-DL:
Ibr = 1,6 mA
Ij = 0,09 mA
Ndet = 1,6/0,09 ≈ 17 pcs.
It is recommended to place such a terminal resistor in the nominal load mode so that the summary current drawing through Rterm and consumed by detectors would be within the limits of 4 mA, that is:
Ial = Ual / Rterm + Ism * Ndet (2)
Where Ial — summary current in an alarm loop; Ual — nominal voltage in an alarm loop; Idet — summary consumption current by detectors in the standby mode; Ism — consumption current of a detector in the standby mode. Ndet — quantity of installed detectors in an alarm loop;
Thus:
Rterm = Ual / (Ism - Ism * Ndet)
Rterm = 12V / (4mA - 0,22mA * 7) ≈ 4,7 KΩ
The limiting resistor in the electric circuit of a detector must be chosen, so that the current increase in AL equals approx. 5 mA when the detector activates. When the internal resistance of the detector in the “Fire” mode equals approx. 500 Ω, the resistance value of the limiting resistor must equal Rterm = 12Â/5mA-0,5 KΩ ≈ 2 KΩ



