Question 5


Question: Is it possible to connect several fire linear detectors “ARTON-DL” to a single fire alarm loop?

Answer: The connection of a few fire linear detectors “ARTON-DL” to a single fire alarm loop is possible only with the application of matching modules “MUSH-DL”, and besides the quantity of “MUSH-DL” must conform to that one of “ARTON-DL”. The connection is accomplished according to the scheme Open in a new window, where Rn=3.6 KΩ, Rterm=2.4 KΩ, Rlim=3.9 KΩ are defined by the type of a control panel.