Question: In what way fire linear detectors “ARTON-DL” should be placed in premises higher than 12 meters?
Answer: The placement of fire linear detectors “ARTION-DL” is carried out in the complete conformity with DBN V.2.5-13-98. It is necessary as a rule to install detectors “ARTON-DL” in two tiers in premises with the height more than 12m, and along with that the right tier should be placed by 4m from the plane. The space between axes must be not more than 7.5m and the distance from an optical axis to a wall – not more than 3.5m.